Marking example in accordance with RL 2014/34/EU, EN IEC 60079-0 ff – Electrical equipment
- Manufacturer and address
- Type number of the product
- Other relevant information for industrial equipment
- Conformity mark (CE)
- Identification number of the notified body which - where required - certified the QA system or examined the products (Category 1 and 2)
- Ex mark
- Equipment group II - other areas (non-mining) Equipment category 2 - gases/vapours G, suitable for Zones 1 and 2 - dusts D, suitable for Zones 21 and 22
- EU-type examination certification notified body’s symbol, year notified body’s registration number
- CoC Certificate of Conformity notified body’s symbol, year notified body’s registration number
- - Explosion protection in compliance with EN IEC 60079-0 ff, Type of protection: flameproof enclosure and increased safety (gas) - Marked Ex d and Ex e, protection by enclosure (dust) - Marked Ex t
- Explosion protection in compliance with EN IEC 60079-0 ff, Type of protection: flameproof enclosure and increased safety (gas) - Marked Ex d and Ex e, protection by enclosure (dust) - Marked Ex t
- Explosion group IIC (above ground, group C), explosion group IIIC (conductible dusts)
- Temperature class T6 (gas), max. surface temperature 80°C (dust)
- Equipment protection level Gb (high protection level) (gas), equipment protection level Db (high protection level) (dust)
- - "X" observe special conditions: e. g. “the light module must be installed in a way that ensures its mechanical protection from impact energy in accordance with EN 60079-0”.
- “U” Ex Component which is not intended to be used alone. CE conformity is certified when installed into a complete operating equipment.
- Ambient temperature
- Marking in accordance with INMETRO (Example)
Marking example in accordance with Directive 2014/34/EU, EN and IEC standards (EN 13463-1ff/ISO 80079-36, -37) – Non-electrical equipment
- Manufacturer and address
- Type number of the product
- Other relevant information for industrial equipment
- Conformity mark(CE)
- dentification number of the notified body which - where required - certified the QA system or examined the products *
- Ex mark
- EEquipment group II - other areas (non-mining) Equipment category 2 - Gases/vapours G, suitable for Zones 1 and 2 - Dusts D, suitable for Zones 21 and 22
- EU-type examination certification Notified body’s symbol, year Notified body’s registration number (only with Category 1)
- - Explosion protection in compliance with EN ISO 80079-36, -37 standards type of protection: constructional safety - Marked Ex h
- Explosion protection in compliance with EN 13463-1ff Type of protection: constructional safety - Marked c
- Explosion protection in compliance with ISO 80079-36, -37 Standards type of protection: constructional safety - Marked Ex h
- Explosion group IIC (above ground, group C)
- Temperature class T6 (gas)
- Equipment protection level Gb (high protection level) (gas)
- - "X" observe special conditions: e. g. The gearbox is to be installed only in certain position.
- "U" Ex Component which is not intended to be used alone. CE conformity is certified when installed into a complete operating equipment. Components don’t have any temperature class.
- Ambient temperature